Calculate Earthing Strip Size for Electrical Equipment’s in Power Distribution Network

EXAMPLE:

Calculate Earthing Strip / Cable Size for Electrical Equipment’s / Panels in Power Distribution Networks.

  • At RMU
  • At Transformer
  • At D.G Set
  • At Main Distribution Panel
  • At Sub Panel-1
  • At Sub Panel-2
1

CALCULATION:

(1) Earthing Strip Size at RMU:

  • Shot circuit capacity at RMU is 18.37 KA for 1 Second.
  • Corrosion in Strip is 1% per year
  • Earthing Strip shall be replaced after 25 Years.
  • Safety Factor for Strip is 1.5
  • Earthing Strip Material is GI

Calculation

  • As per IS: 3043, clause 17.2.2.1:
  • Cross section area of Earthing Strip (A) =(Isc x√t)/k
  • Where Isc= Shot circuit current capacity in Ampere.
  • t= Time for Shot circuit current in Second.
  • K= Material Constant
Bare Conductor Material with No Risk of Fire or Danger to any Other Touching or Surrounding Material
TABLE 11A (IS:3043)
MaterialK value (1 second)K value (2 second)
Steel8046
Aluminum12673
Copper205118
  • Cross section area of Earthing Strip (A) = (Isc x√t)/k
  • Cross section area of Earthing Strip (A) = (18.37×1000 x√1)/80
  • Cross section area of Earthing Strip (A) = 229.69 Sq.mm
  • Allowable corrosion =1% per Year
  • No of Year for replacement = 25 Year
  • Allowable corrosion in 25 Years = 229.69x1x25% =57.40 Sq.mm
  • Allowable Safety Factor = 229.69×1.5%=3.44 Sq.mm
  • Required Earthing Strip size = Cross sectional area + Total Corrosion allowance + Safety factor
  • Required Earthing Strip size=229.69+57.40+3.44 Sq.mm
  • Required Earthing Strip size=290.47 Sq.mm
  • Proposed GI Earthing Strip shall be 50×6 mm = 300 Sq.mm.
  • Here Proposed Earthing Strip Size > Required Earthing Strip Size
  • Proposed Earthing Strip is OK

(2) Earthing Strip Size at Transformer:

  • Shot circuit capacity at Transformer is 25.32 KA for 1 Second.
  • Corrosion in Strip is 1% per year
  • Earthing Strip shall be replaced after 25 Years.
  • Safety Factor for Strip is 1.5
  • Earthing Strip Material for Transformer Neutral is Copper
  • Earthing Strip Material for Transformer Body is GI

Calculation

  • For Neutral
  • As per IS: 3043, clause 17.2.2.1:
  • Cross section area of Earthing Strip (A) =(Isc x√t)/k
  • Where Isc= Shot circuit current capacity in Ampere.
  • t= Time for Shot circuit current in Second.
  • K= Material Constant
Bare Conductor Material with No Risk of Fire or Danger to any Other Touching or Surrounding Material
TABLE 11A (IS:3043)
MaterialK value (1 second)K value (2 second)
Steel8046
Aluminum12673
Copper205118
  • Cross section area of Earthing Strip (A) = (Isc x√t)/k
  • Cross section area of Earthing Strip (A) = (25.32×1000 x√1)/205
  • Cross section area of Earthing Strip (A) = 125.51 Sq.mm
  • Allowable corrosion =1% per Year
  • No of Year for replacement = 25 Year
  • Allowable corrosion in 25 Years = 125.51 x1x25% =30.87 Sq.mm
  • Allowable Safety Factor = 125.51 x1.5%=1.85 Sq.mm
  • Required Earthing Strip size = Cross sectional area + Total Corrosion allowance + Safety factor
  • Required Earthing Strip size=125.51+30.87+1.85 Sq.mm
  • Required Earthing Strip size=156.24 Sq.mm
  • Proposed Cu Earthing Strip shall be 32×6 mm = 192 Sq.mm.
  • Here Proposed Earthing Strip Size > Required Earthing Strip Size
  • Proposed Earthing Strip is OK
  • For Body
  • As per IS: 3043, clause 17.2.2.1:
  • Cross section area of Earthing Strip (A) =(Isc x√t)/k
  • Where Isc= Shot circuit current capacity in Ampere.
  • t= Time for Shot circuit current in Second.
  • K= Material Constant
Bare Conductor Material with No Risk of Fire or Danger to any Other Touching or Surrounding Material
TABLE 11A (IS:3043)
MaterialK value (1 second)K value (2 second)
Steel8046
Aluminum12673
Copper205118
  • Cross section area of Earthing Strip (A) = (Isc x√t)/k
  • Cross section area of Earthing Strip (A) = (25.32 x1000 x√1)/80
  • Cross section area of Earthing Strip (A) = 316.5 Sq.mm
  • Allowable corrosion =1% per Year
  • No of Year for replacement = 25 Year
  • Allowable corrosion in 25 Years = 316.5 x1x25% =79.12 Sq.mm
  • Allowable Safety Factor = 316.5 x1.5%=4.74 Sq.mm
  • Required Earthing Strip size = Cross sectional area + Total Corrosion allowance + Safety factor
  • Required Earthing Strip size=316.5+79.12+4.74 Sq.mm
  • Required Earthing Strip size=400.37 Sq.mm
  • Proposed GI Earthing Strip shall be 75×6 mm = 450 Sq.mm.
  • Here Proposed Earthing Strip Size > Required Earthing Strip Size
  • Proposed Earthing Strip is OK

(3) Earthing Cable Size at D.G Set:

  • Shot circuit capacity at D.G Set is 10KA for 1 Second.
  • Corrosion in Strip is 1% per year
  • Earthing Strip shall be replaced after 25 Years.
  • Safety Factor for Strip is 1.5
  • Earthing Wire Material is Copper, XLPE Insulated

Calculation

  • As per IS: 3043, clause 17.2.2.1:
  • Cross section area of Earthing Strip (A) =(Isc x√t)/k
  • Where Isc= Shot circuit current capacity in Ampere.
  • t= Time for Shot circuit current in Second.
  • K= Material Constant
Insulated Protective Conductors Not Incorporated in Cables or Bare Conductors Touching Other Insulated Cables
TABLE 11B (IS:3043)
MaterialK value (1 second)K value (3 second)
Copper , PVC Insulated13679
Copper, Rubber Insulated15092
Copper, XLPE Insulated17098
Aluminum, PVC Insulated9052
Aluminum, Rubber Insulated10661
Aluminum, XLPE Insulated11265
Steel, PVC Insulated4928
Steel, Rubber Insulated5833
Steel, XLPE Insulated6236
  • Cross section area of Earthing Strip (A) = (Isc x√t)/k
  • Cross section area of Earthing Strip (A) = (10×1000 x√1)/170
  • Cross section area of Earthing Strip (A) = 58.82 Sq.mm
  • Allowable corrosion =1% per Year
  • No of Year for replacement = 25 Year
  • Allowable corrosion in 25 Years = 58.82x1x25% =14.70 Sq.mm
  • Allowable Safety Factor = 58.82 x1.5%=0.88 Sq.mm
  • Required Earthing Strip size = Cross sectional area + Total Corrosion allowance + Safety factor
  • Required Earthing Strip size=58.82+14.7+0.88 Sq.mm
  • Required Earthing Strip size=74.41 Sq.mm
  • Proposed Earthing Single Core Copper, XLPE Cable=95 Sq.mm
  • Here Proposed Earthing Cable Size > Required Earthing Cable Size
  • Proposed Earthing Cable is OK

(4) Earthing Strip Size at Main Panel :

  • Shot circuit capacity at Main Panel is 21 KA for 1 Second.
  • Corrosion in Strip is 1% per year
  • Earthing Strip shall be replaced after 25 Years.
  • Safety Factor for Strip is 1.5
  • Earthing Strip Material is GI

Calculation

  • As per IS: 3043, clause 17.2.2.1:
  • Cross section area of Earthing Strip (A) =(Isc x√t)/k
  • Where Isc= Shot circuit current capacity in Ampere.
  • t= Time for Shot circuit current in Second.
  • K= Material Constant
Bare Conductor Material with No Risk of Fire or Danger to any Other Touching or Surrounding Material
TABLE 11A (IS:3043)
MaterialK value (1 second)K value (2 second)
Steel8046
Aluminum12673
Copper205118
  • Cross section area of Earthing Strip (A) = (Isc x√t)/k
  • Cross section area of Earthing Strip (A) = (21 x1000 x√1)/80
  • Cross section area of Earthing Strip (A) = 262.5 Sq.mm
  • Allowable corrosion =1% per Year
  • No of Year for replacement = 25 Year
  • Allowable corrosion in 25 Years = 262.5 x1x25% =65.62 Sq.mm
  • Allowable Safety Factor = 262.5 x1.5%=3.93 Sq.mm
  • Required Earthing Strip size = Cross sectional area + Total Corrosion allowance + Safety factor
  • Required Earthing Strip size=262.5+65.62+3.93 Sq.mm
  • Required Earthing Strip size=332.06 Sq.mm
  • Proposed GI Earthing Strip shall be 75×6 mm = 450 Sq.mm.
  • Here Proposed Earthing Strip Size > Required Earthing Strip Size
  • Proposed Earthing Strip is OK

(5) Earthing Strip Size at Sub Panel-1 :

  • Shot circuit capacity at Sub Panel-1 is 11 KA for 1 Second.
  • Corrosion in Strip is 1% per year
  • Earthing Strip shall be replaced after 25 Years.
  • Safety Factor for Strip is 1.5
  • Earthing Strip Material is GI

Calculation

  • As per IS: 3043, clause 17.2.2.1:
  • Cross section area of Earthing Strip (A) =(Isc x√t)/k
  • Where Isc= Shot circuit current capacity in Ampere.
  • t= Time for Shot circuit current in Second.
  • K= Material Constant
Bare Conductor Material with No Risk of Fire or Danger to any Other Touching or Surrounding Material
TABLE 11A (IS:3043)
MaterialK value (1 second)K value (2 second)
Steel8046
Aluminum12673
Copper205118
  • Cross section area of Earthing Strip (A) = (Isc x√t)/k
  • Cross section area of Earthing Strip (A) = (11 x1000 x√1)/80
  • Cross section area of Earthing Strip (A) = 137.5 Sq.mm
  • Allowable corrosion =1% per Year
  • No of Year for replacement = 25 Year
  • Allowable corrosion in 25 Years = 137.5 x1x25% =34.37 Sq.mm
  • Allowable Safety Factor = 137.5 x1.5%=2.06 Sq.mm
  • Required Earthing Strip size = Cross sectional area + Total Corrosion allowance + Safety factor
  • Required Earthing Strip size=137.5+34.37+2.06 Sq.mm
  • Required Earthing Strip size=173.93 Sq.mm
  • Proposed GI Earthing Strip shall be 32×6 mm = 192 Sq.mm.
  • Here Proposed Earthing Strip Size > Required Earthing Strip Size
  • Proposed Earthing Strip is OK

(5) Earthing Strip Size at Sub Panel-2 :

  • Shot circuit capacity at Sub Panel-2 is 6 KA for 1 Second.
  • Corrosion in Strip is 1% per year
  • Earthing Strip shall be replaced after 25 Years.
  • Safety Factor for Strip is 1.5
  • Earthing Strip Material is GI

Calculation

  • As per IS: 3043, clause 17.2.2.1:
  • Cross section area of Earthing Strip (A) =(Isc x√t)/k
  • Where Isc= Shot circuit current capacity in Ampere.
  • t= Time for Shot circuit current in Second.
  • K= Material Constant
Bare Conductor Material with No Risk of Fire or Danger to any Other Touching or Surrounding Material
TABLE 11A (IS:3043)
MaterialK value (1 second)K value (2 second)
Steel8046
Aluminum12673
Copper205118
  • Cross section area of Earthing Strip (A) = (Isc x√t)/k
  • Cross section area of Earthing Strip (A) = (6 x1000 x√1)/80
  • Cross section area of Earthing Strip (A) = 75.0 Sq.mm
  • Allowable corrosion =1% per Year
  • No of Year for replacement = 25 Year
  • Allowable corrosion in 25 Years = 75 x1x25% =18.75 Sq.mm
  • Allowable Safety Factor = 75 x1.5%=1.12 Sq.mm
  • Required Earthing Strip size = Cross sectional area + Total Corrosion allowance + Safety factor
  • Required Earthing Strip size=75+18.75+1.12 Sq.mm
  • Required Earthing Strip size=94.87 Sq.mm
  • Proposed GI Earthing Strip shall be 25×6 mm = 150 Sq.mm.
  • Here Proposed Earthing Strip Size > Required Earthing Strip Size
  • Proposed Earthing Strip is OK

CONCLUSION:

  • At RMU=GI Earthing Strip: 50x6MM
  • At Transformer Neutral=CU Earthing Strip: 32x6MM
  • At Transformer Body=GI Earthing Strip: 75x6MM
  • At D.G Set=CU, XLPE Earthing Cable: 1Cx95 SQ.MM
  • At Main Distribution Panel=GI Earthing Strip: 75x6MM
  • At Sub Panel=1=GI Earthing Strip: 32x6MM
  • At Sub Panel-2=GI Earthing Strip: 25x6MM.